OEM / Vertical Rack Mount Enclosure Manufacturer
Telecom, Traffic, Wimax, LTE, Security
Outdoor NEMA 3, 3R, 4, 4X Cabinet Enclosures
Outdoor Enclosure with Front and Rear Door
Total Occupied Space: 78.75″H x 28.5W x 36.7″D
Top Compartment: 49.56″H,
Bottum Compartment: 25.69″H
Useable Depth: Maximum: 30.5” Minimum: 28.75″
Front and Rear sets of Adjustable 19” or 23” racking.
Racking Rails 48.72″H / Tapped 10/32, / (2) Pass Thru Holes.
Heavy Duty Lifting Hooks.
Powder Baked on Textured White Paint.
HT-300 300 Watt Heater Strip 110 Volts
Dual compartment design, 600 cfm direct air cooled (DAC) top
compartment and fan cooled battery compartment using (2) 5”,
48v, 110cfm fans and thermostat.
45”H x 26”W x 10”D Side box with removable plywood back-plate
with a total of (5) 2” cable pass through openings;
(4) for the
primary compartment and (1) for the battery cables.
12” Copper ground bar on 14”risers with isolators.
Dual panel AC load center with 50amp back-up generator plug.
Interior convenience outlets and 220V supplied junction box for
DC power system. See electrical layout.
DAC (direct air cooled) system is driven by a 10” diameter, 600
cfm, 48v fan drawing air through a 2” thick MERV 16, GR-487 Salt
Fog filter.
UL & CSA Certified
30″H X 25″W X 25″D(19″ Racking)
2400 BTU 230 Volts with 400 Watts of Heat
Ext. Generator Plug
Door Alarm Switches
Fluorescent Light
Spool-Up Side Box
Ground Bar
R3.3 Insulation
R7-30DXCW(120) = 120 Volt version